Compressor control and surveillance
In
Set point 1
enter the motor top load power as stated on the name plate. In
Set point 2
a lower value
can be entered for periods requiring less power. Switch between the two set points by opening or closing
a digital input, see wiring diagrams.
Open input =
Set point 1
. See also
3.5.10
Thermistor connection
If the motor is fitted with thermistors to protect the motor temperature, these can be connected directly to
a digital input. See wiring diagrams.
If the motor temperature rises excessively, the compressor will stop.
3.5.11
COP set-up
UniSAB III can be set for measuring compressor COP (Coefficient of Performance), mechanical effi-
ciency and Carnot efficiency.
Together with suction/discharge pressure and temperature, the following values form the basis of the
calculations:
•
Temperature of chilled liquid before evaporator.
•
Volume flow of cooling gas on pressure side (m
3
/h).
•
Motor power consumption in kW.
•
Motor efficiency.
The COP function is enabled or disabled in the menu
Configuration/Plant
by setting COP active =
Yes
or
No
.
The calculated COP values are shown in the picture
Service/Diagnose/Software/COP
. A more compre-
hensive description of the COP function and its setting is included in the manual UniSAB III-COP.
3.5.12
HP on two-stage
This function is used on two-stage plants to start HP compressors by force.
HP on two-stage
must have been selected in the menu
Setup/Configuration/Plant
. The function only
works in
Remote/Multisab
.
A compressor is started by force by closing the input
Ext start normal stop
. The first compressor is now
going to start within the period of time set in the timer
Start h press
. After this, the compressors will regu-
late normally on the capacity regulator.
Please note that the last (stopping) compressor in operation in a Multisab system (usually the no. 1 com-
pressor in the starting sequence) will not stop on the timer
Delay before stop
. It can only be stopped by
opening the input
Ext start normal stop
, which makes the compressor stop for a moment.