Engineering manual - UniSAB III 1.10.8
001930 en 2021.06
115/346
Compressor control and surveillance
Alarm surveillance
During start the following alarms are delayed:
Low oil pressure
45 sec.
High filter diff. pressure
600 sec.
Low superheat
300 sec.
High superheat
300 sec.
Low/high oil temperature
300 sec.
The delayed alarms are described in section
.
Stopping sequence
When a SAB 193-233-283-355 compressor stops, UniSAB III will attempt to move the capacity slide be-
low 5% position. The solenoid valves for decreasing capacity and Vi position are activated for maximum
300 seconds. If the capacity slide is not below 5% within the 300 seconds a
Capacity error
shutdown will
be issued.
Balance piston for SAB 355
For SAB 355, the AUX output is dedicated for control of the balance piston. Choose the AUX output to
be activated
At max. cap.
in the menu
Compressor control – user functions
and set the
Signal high
limit
to 70% referring to slide capacity.
3.3.19
SAB 193, 233, 283 and 355 without oil pump
The compressors are equipped with capacity slide and automatic Vi-control.
If the compressor is equipped with a frequency converter (VSD) see subsection
6: Rotatune
for additional set-up of UniSAB III.
The compressor has no oil pump.
Starting sequence
When the compressor has received starting permission, UniSAB III will check whether the capacity slide
is in minimum position. If the capacity slide is higher than 5% position, the solenoid valve for decreasing
capacity slide position will be activated for maximum 300 seconds. If the capacity slide is still higher than
5% position, a
Capacity error
shutdown will be issued and the compressor will not start. If the capacity
slide is lower than 5% position the compressor is allowed to start.
Before start-up UniSAB III will also check the oil level and temperature in the oil separator. If the oil level
is too low an
oil system error alarm
will be issued. No signal from the oil level switch during operation will
result in shutdown after a delay of 30 seconds. If the oil temperature is lower than the set limits a
low oil
separator temp
alarm or shutdown will be issued. The limits for oil separator temperature can be set in
the menu
Control values/Oil/Separator temp/Limits
.
If the oil level switch is active and the separator temperature is above the shutdown limit, the compressor
will start.