Engineering manual - UniSAB III 1.10.8
134/346
001930 en 2021.06
Compressor control and surveillance
Depending on the compressor type, the default settings and the min. and max. settings are as listed
here;
default value [min., max.]:
Compressor
Motor rpm min.
Motor rpm max.
SMC/HPC
500 [500,1000]
1500 [1100,1800]
HPX
500 [500,1000]
1800 [1100,1800]
CMO/HPO
700 [700,1000]
1800 [1100,1800]
The minimum compressor capacity for a typical 4-pole motor at 50 Hz running
Speed
mode will be:
Compressor type
Standard motor
Special motor
SMC/HPC 104 and HPX 704
47%
700 rpm
33%
500 rpm
SMC/HPC 106 and HPX 706
47%
700 rpm
33%
500 rpm
SMC/HPC 108 and HPX 708
17%
500 rpm
TSMC 108
11%
500 rpm
SMC/HPC 112 and HPX 712
17%
500 rpm
SMC/HPC 116 and HPX 716
8%
500 rpm
TSMC 116
6%
500 rpm
CMO/HPO 24
50%
900 rpm
39%
700 rpm
CMO/HPO 26
19%
700 rpm
CMO/HPO 28
19%
700 rpm
TCMO 28
13%
700 rpm