Engineering manual - UniSAB III 1.10.8
36/346
001930 en 2021.06
Manual stop
You can stop the compressor immediately by pressing
. Compressor status in the info bar will be
cap.
slide down
or
pause
depending on compressor type. The light diode above the start key will be off.
For SAB 109, 133 and 159 you will experience a time delay from pressing the stop key and until the
compressor stops. This is normal and the reason is that the controller closes the automatic stop valve
before the compressor motor is stopped, which takes 40 seconds.
1.2.9
Shutdown and alarm acknowledgement
A compressor
shutdown
is acknowledged by pressing
/RESET. If the cause of shutdown is no lon-
ger present the shutdown message will disappear from the shutdown queue. A shutdown stops the com-
pressor immediately and is indicated by quick red flashes in the light diode above the start key. An
acknowledged shutdown where the shutdown cause is still present is indicated by slow red flashes in
the light diode.
A compressor
alarm
is automatically acknowledged when the alarm cause is no longer present and the
alarm message will disappear from the alarm queue. An alarm does
not
stop the compressor. It is indi-
cated by quick yellow flashes in the light diode above the start key.