Engineering manual - UniSAB III 1.10.8
326/346
001930 en 2021.06
Version no.
Description
1.0.9.4
The new
Pay
function for
Remote Monitoring
, i.e. E-mail trending and alarm reports to
the central remote monitoring server, has been changed. This function is now enabled
as standard when UniSAB III leaves the factory.
This change is part of the iRIS initiative which proclaims that all new UniSAB III controls
inside Europe will be set up to report information to the central remote monitoring
server.
Two SAB 157 HR compressors would not always run quite as expected in Multisab, i.e.
the deviation between master and slave parallel capacity could be higher than ex-
pected compared to other Rotatune screw compressors. This has now been corrected.
The file handling has been improved. UniSAB III can now handle the rare situation that
a file is corrupted in the file folder as well as in the back up folder.
The automatic contrast adjustment of the display would sometimes shortly make the
display dark. To prevent this, the contrast handling has been improved by extending
the filtering of the temperature reading from the display.
1.0.9.6
The
Pay
function for e-mail user, i.e. e-mail shutdown and alarm reports to the user e-
mail recipients, has been changed. This function is now as standard enabled when Uni-
SAB III leaves the factory.
This change is part of the iRIS initiative in which all new UniSAB III controls in Europe
will be set up to report information to the central remote monitoring server.
The zip function is now enabled for trend files sent to the remote monitoring server.
SMTP account login is now enabled for the remote monitoring SMTP server and the e-
mail user SMTP server.
Separate port number set-up is now enabled for the Remote Monitoring SMTP server
and the e-mail user SMTP server.
Address e-mail brackets are now enabled for the SMTP server session.
The xml file check has been improved; xml files are checked using the xml file handler
error code. If an xml file should be corrupt, it will be deleted and UniSAB III is restarted.
Regulator set point change was not possible for the chiller level regulator when the
compressor was running in manual and in limitation. This has now been corrected.
It has been reported from a few plants that the indexing of history shutdown log could
fail after a version upgrade. This has now been corrected.