Engineering manual - UniSAB III 1.10.8
64/346
001930 en 2021.06
2.3
Shutdowns and alarms list with id nos.
2.3.1
Shutdowns and alarms for screw compressors
Shutdown/alarm
Id
Danbuss
Profibus/
Modbus
Low suction pressure
alarm + shutdown 5)
31
31
High suction pressure
alarm
32
32
Low suction gas superheat
alarm + shutdown
33
33
High suction gas superheat
alarm + shutdown
34
34
Low discharge pressure
shutdown
35
35
High discharge pressure
alarm + shutdown
36
36
High discharge temperature
alarm + shutdown
37
37
Low oil pressure (differential pressure)
alarm + shutdown
38
38
Low brine/intermed. gas temperature
alarm + shutdown
39
39
Low discharge temperature
alarm
40
40
Low oil temperature
alarm + shutdown
41
41
High oil temperature
alarm + shutdown
42
42
High oil filter differential pressure
alarm + shutdown
43
43
Oil system error (oil level/flow switch)
shutdown
44
44
Capacity error
alarm + shutdown 1)
45
45
Compressor motor overload
shutdown
46
46
Compressor motor error/emergency stop/
HP
shutdown
47
47
Oil pump error
alarm + shutdown 2) 4)
48
48
High motor temperature (thermistor)
shutdown
49
49
PMS error
shutdown
55
55
No starting permission
alarm
56
56
High brine/intermed. gas temperature
alarm + shutdown
58
58
Full flow pump error
alarm + shutdown 2)
62
62
Oil rectifier error
alarm
64
64
Wrong starting number in sequence
alarm
65
65
Low external input signal
alarm + shutdown
67
67
High external input signal
alarm + shutdown
68
68
Low discharge gas superheat
alarm + shutdown
69
69
Discharge pressure overload
shutdown
70
70
Evolution, shutdown from PLC
shutdown
71
71
Evolution, no communication to PLC
shutdown
72
72
Limiter, suction pressure
alarm
73
73
Limiter discharge pressure
alarm
74
74
Limiter process out (brine) temperature
alarm
75
75
Cooling fan error
shutdown
82
75
Limiter hot water
alarm
76
76
VI position error
shutdown
83
76
Low lubricating pressure
alarm + shutdown
84
77
Liquid slugging
shutdown
NA
78
Watch the oil pressure
alarm
79
79
Oil log
Shutdown
NA
79
No real time clock
alarm
NA
80
Low main oil pressure
shutdown
NA
80
Frick lubricating pressure low
alarm
NA
81
Low oil circuit pressure
shutdown
NA
81
High oil diff pressure
alarm
NA
82