Engineering manual - UniSAB III 1.10.8
132/346
001930 en 2021.06
Compressor control and surveillance
Fig. 21: Capacity vs speed diagram,
SMC 116 E with CFA 140/200
coupling.
For CMO types and a standard setting where minimum speed is set to 700 [rpm], motor rpm min. 2 is
set to 900 [rpm] and maximum speed is 1800 [rpm], the reciprocating compressor will be step/speed
regulated up to 50% and then speed regulated between 50% and 100%.
Capacity vs speed diagram
, S MC 11 6 E VS D wi th C F A140/200 coupling
Minimum speed: 700 rpm
Speed
(rpm)
Capacity
%
0
0
5
1
0
0
0
1
0
0
5
0
0
1
0
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
10
0
Black
line: SPEED mode (optimised for best regulation)
Red line: S
T EP mode (optimised for best COP)
4
cyl
8
cyl
Blue line: both SPEEDand STEP mode
Dashed line
s : transient operation only
Note:
Actual allowed speed range depends on operating conditions and motor selection.
Dotted red line shows
regulation by utilising total
unloading and/or compressor
start/stop
16
cyl
12
cyl