Engineering manual - UniSAB III 1.10.8
001930 en 2021.06
217/346
point for this value is entered in
Control values/Discharge/Temperature/Control, Set point 2
. The set
point has a fixed hysteresis of 5
°
K.
Example:
Sp2 = 90
°
C. Cooling starts at 90
°
C and stops at (90-5) = 85
°
C.
Adjusting range: -20°C-+150°C.
Factory value: 100
°
C.
The regulator controls the solenoid valve through the liquid injection digital output.
6: Oil rectifier
No
Yes
The oil rectifying function is used on brine plants in marine execution. If selecting this function also check
the timers
Oil Rectifying Start
,
Oil Rectifying Delay
and
Oil Rectifying Blocked
.
7: Oil flow control
No
Yes
Select
Yes
for compressor types SAB 193 H–355 H and SAB 273 S to enable
oil flow control
and
dis-
charge temperature difference
supervision.
The
oil flow control
PID regulator controls a motor valve on AO1 with the
motor speed ratio
as input sig-
nal. At raising RPM ratio, the regulator must open the motor valve.
When the compressor is stopped (motor feedback is OFF), the motor valve must not be closed, but the
regulator must continue in operation.
When
oil flow control
is enabled, the two parameters
oil flow open max
(valve opening degree at max.
speed) and
oil flow open min
(valve opening degree at min. speed) can be set:
The motor valve opening degree is given as: AO1 [%] = K
0
+ K
1
x
motor speed ratio
Where:
motor speed ratio
= actual motor rpm /
motor rpm max
K
0
=
oil flow open max
– K
1
K
1
= (
oil flow open max – oil flow open min
) / (1 –
motor rpm min / motor rpm max
)
The supervision of
low discharge temperature difference
is active when the compressor is running at
“Full capacity”.
The alarm
low discharge temperature difference
is released if the discharge temperature difference is
below low alarm limit.
See detailed description in subsection
2.2.44 Low discharge temperature difference alarm
.
Note:
When the
oil flow control
parameter is enabled, the oil cooling parameter
HLI 4-20mA
cannot be
set.
8: Oil flow open max
5 to 100% [70%]
This parameter is used when the
oil flow control
function is enabled. It defines the valve opening degree
at maximum speed.
The
oil flow open max
parameter is used for the
oil flow control
function, see detailed description under
7: Oil flow control
above.