Engineering manual - UniSAB III 1.10.8
190/346
001930 en 2021.06
Set-up/Configuration
No.
Function
Use
Choices
Plant
1
Refrigerant **
1/2
Not defined, R717, R22, R502, R23, R404A,
R134A, R507, R410A, R407C, R744, R1270,
R290, R000, R600
2
Compressor *
1/2
1-14
3
Start
1/2
1-14
4
System
1/2
1-14
5
Common evap./cond.
1/2
N/N, N/Y, Y/N, Y/Y
6
HP on two-stage
1/2
No, Yes
7
High limit
1/2
0 to 100%
8
Capacity output AO1
1/2
No, Yes
9
Capacity down blocked
1/2
No, Yes
10
Take over
1
No, Yes
11
COP active
1/2
No, Yes
12
Chiller/Heat pump
1/2
No, Yes
13
Process out temp.
1/2
No, Yes
14
Process in temp.
1/2
No, Yes
15
Oil return separator
1/2
No, Yes
16
Oil return evaporator
1/2
No, Yes
17
By-pass start
1/2
No, Yes
18
Flow evaporator
1/2
No, Yes
19
Flow condenser
1/2
No, Yes
20
Liquid level lim.
1
No, Yes
21
Level control
1/2
Off/LP/HP/DX
22
Ext PT100
1/2
No, Yes
23
Flow factor
1/2
0 to 10,000 m
3
/hour
24
Liquid subcool
1/2
0 to 99.9°C/R
25
PMS feedback fixed
1/2
No, Yes
Oil system
1
Oil pump
2
No, Yes
2
Full flow pump
2
No, Yes
3
Oil cooling
1/2
None, Normal, HLI/BLI, Thermo pump, 3-way valve,
HLI-AKV, HLI 4-20 mA, Thermo pump internal
4
Oil controller
2
I, PID
5
Water cooling
1
No, Yes
6
Oil rectifier
1/2
No, Yes
7
Oil flow control
2
No, Yes
8
Oil flow open max.
2
5.0 to 100.0 % [70.0 %]
9
Oil flow open min.
2
5.0 to 10.0 % [5.0 %]
10
Balance pressure reduction
2
No, Yes
11
Separator velocity reference
2
0.00 to 10.00
12
Separator velocity compression
ratio
2
0.00 to 99.99
13
Separator temperature control
2
No, Yes
14
Oil low alarm coefficient
2
0.25 to 1.00 / 0.50 to 1.00
15
Oil unload coefficient
2
1.0 to 2.0 [1.25]
16
Oil load coefficient
2
1.0 to 2.0 [1.30]
Содержание SABROE Unisab III Control
Страница 1: ...UniSAB III control Version 1 10 8 Engineering manual EN...
Страница 2: ......
Страница 347: ......