Engineering manual - UniSAB III 1.10.8
001930 en 2021.06
55/346
2.2.15
Wrong starting number in sequence
The reason for the alarm is that two or more compressors have the same starting number and the same
system number.
2.2.16
Limiting suction pressure
The alarm indicates that the suction pressure limiter is active, i.e. the suction pressure is within the limit-
er neutral zone or below the alarm limit.
2.2.17
Limiting discharge pressure
The alarm indicates that the discharge pressure limiter is active, i.e. the discharge pressure is within the
limiter neutral zone or above the alarm limit.
2.2.18
Limiting process out temperature
The alarm indicates that the process out temperature limiter is active, i.e. the process out temperature is
within the limiter neutral zone or below the alarm limit.
2.2.19
Limiting hot water
The alarm indicates that the hot water temperature limiter is active, i.e. the hot water temperature is with-
in the limiter neutral zone or above the alarm limit.
2.2.20
Limiting discharge temperature
The alarm indicates that the discharge pipe temperature limiter is active. See section
High discharge pipe temperature
.
2.2.21
Start-up limiter
SABflex and SABCube compressors (SAB 109
→
→
159)
The alarm indicates that the SSSTV valve is closed and that the speed might be limited to 1.000 [rpm]
during start-up. This will be caused by too high external (or internal) suction pressure or too low oil pres-
sure. The start-up limiter can maximum be active for the time set in timer
Max. start-up time
, which de-
fault is set to 600 sec.
When the
Max. start-up time
timer is running the
Start-up limiter
is an alarm. When the
Max. start-up
time
timer runs out the
Start-up limiter
alarm is converted into a shutdown and the compressor is
stopped.
2.2.22
Start up RPM limiter
High-pressure compressors (SAB 157 HR)
The alarm indicates that the speed is limited to minimum speed, default 1,000 [rpm] during start-up be-
cause of too high suction pressure.
The start-up limiter can maximum be active for the time set in timer
Start RPM limiter
(default 300 sec-
onds). When the limiter is active the
Start RPM limiter
timer is running and a
Start-up RPM limiter
alarm
is shown. If the
Start RPM limiter
timer runs out while the limiter is still active, the compressor is stopped
by a shutdown
Start RPM limiter error
.
2.2.23
Lube pressure unload alarm
High-pressure compressors (SAB 157 HR)
This alarm indicates that the oil lubricating pressure is low and that the plug valve therefore has been un-
loaded. See Fig. 7.