Engineering manual - UniSAB III 1.10.8
338/346
001930 en 2021.06
Version no.
Description
1.1.0.8
Screws - Vi regulator
There was an issue in the Vi regulator: when the compressor was in Vi mode and the
two slides were pressed together, the neutral zone used by the capacity slide did not
synchronise with the neutral zone used by the Vi slide. This has now been corrected.
SABflex - backspin supervision
For SABflex with Danfoss drive, the backspin supervision was not enabled when the
compressor was stopped, i.e. in state Pause. This has now been corrected.
Recips - water cooling, off delay by shutdown
In case of a shutdown or emergency stop, the water cooling digital output was set inac-
tive immediately, regardless if the discharge temperature was above set point 1. The
off delay timer for water cooling should be delayed, as by normal stop, when discharge
temperature is above set point 1. This has now been corrected.
Discharge pressure limiter - overload shutdown
There was no correlation between the start of the discharge overload timer and the
state of the discharge pressure limiter. The discharge overload timer should only count
down when the discharge pressure limiter was in active state and working to reduce
Yield. This has now been corrected.
Multisab problem for recips without VSD
When a recip (#1) is running in Remote/Multisab and the next recip (#2) is switched
from Remote/Multisab into Auto, recip (#2) would not start before recip (#1) was run-
ning 100% or stopped or powered off. This has now been corrected.
Multisab parallel offset problem for screw with VSD
When two screws with VSD were running and the third screw was in manual, the fol-
lowing compressors would start but would not increase capacity. This has now been
corrected.
R290 refrigerant table
An error in the table, for bar and psi at 32 bar, has now been corrected.
ResourceBundles
A truncation issue for long alarm info text strings has been corrected.
The EmailService.xml file has been updated.
The logo for the windows HMI simulator has been updated.
The SabSIM simulator has been updated to release 1.04.
The Keygen security has been improved; now only allowing the Keygen server to gen-
erate keys.