Compressor control and surveillance
Starting sequence
Once the compressor has received starting permission, check that the capacity slide is in minimum posi-
tion. The oil pump is started and oil will be pumped into the compressor lubrication system. To avoid
shutdown the oil flow switch must be activated within 45 seconds.
When the oil flow switch is activated, the compressor will start.
The pump will operate for a minimum of 60 seconds and stop if the differential pressure is higher than
Set point 2
as described above.
Alarm surveillance
During start the following alarms are delayed:
Low oil pressure
45 sec.
High filter diff. pressure
300 sec.
Low superheat
300 sec.
High superheat
300 sec.
Low/high oil temperature
300 sec.
See also section
3.3.13
GSV/RWF with oil pump
The pump is used for prelubrication and to maintain a minimum oil pressure level during operation. The
pump is started and stopped in accordance with the compressor differential pressure (discharge pres-
sure - suction pressure) during operation.
The difference is set in the picture
Oil/Pressure/Control
whereupon
Set point 1
and
Set point 2
will
appear.
Set point 1
is the pump start pressure and
Set point 2
is the pump stop pressure. Consequently,
Set
point 1
must be set for the lowest pressure level.
Normal setting for GSV/RWF:
Set point 1 = 2.5 bar.
Set point 2 = 4.0 bar.
If the compressor differential pressure is below
Set point 1
during operation, the pump will start
immediately.
When the compressor differential pressure has been higher than
Set point 2
for 60 seconds, the pump
will stop.
Starting sequence
When the compressor has received starting permission, it must be checked if the capacity slide is still in
minimum position. If the compressor stops, make sure that the capacity slide is in minimum position.
Before start-up the oil level switch in the oil separator must be active. If not, a shutdown for oil system er-
ror will be issued.
No signal from the oil level switch will result in shutdown after a delay of 60 seconds from compressor
start or during operation.
If the oil level switch is active, the prelubrication period will begin and oil will be pumped into the com-
pressor lubrication system. When the time period has expired, the compressor will start and the pump
will run for min. 60 seconds. The pump stops if the differential pressure is higher than
Set point 2
.