Engineering manual - UniSAB III 1.10.8
001930 en 2021.06
179/346
Suction Ramp Load
shows the state of the suction ramp function. See subsection
ers, Suction ramp
.
The value shows the actual suction pressure limit which will be equal to the suction pressure set point if
the suction ramp is not active. When the suction ramp is active, the value will decrease by 1°C every N
seconds, where N is the selected value of the
Suct. Ramp
timer.
Suction Superheat
is the same as
suction superheat set point 2
used by the
High Discharge Pipe Tem-
perature
Limiter. See subsection
.
Capacity
and
Brake Delay
are explained in subsection
3.9.1 Electrical slide control
.
LAN load high
is used in case the UniSAB III interface becomes very slow, or, in the more extreme
cases, if UniSAB III restarts when connected to LAN. Changing the parameter
LAN load high
from the
default setting No to Yes will lower the communication impact on UniSAB III. See also subsection
Supervisor password
In this picture, all supervisor password applications including date and hour are registered.
Examine all parameters
In this picture all parameters in UniSAB III can be inspected. Use
and
to inspect the list.
Содержание SABROE Unisab III Control