Engineering manual - UniSAB III 1.10.8
001930 en 2021.06
87/346
Compressor control and surveillance
Fig. 15: Climate compensation, example 1
The settings in the drawing are:
Sp1 = 12
°
C at To = 0
°
C and
Sp2 = 4
°
C at To = 30
°
C.
Note that
Sp1
belongs to the lowest and
Sp2
to highest outside temperature.
The straight line in Fig. 15 indicates the inlet temperature variation under influence of the outside
temperature.
Select the menu
Control values/Process temp./Process out temp./Control
and go to
Set point 1
and
Set
point 2
with
.
Give
Set point 1
the value Sp1 = 12
°
C from Fig. 15.
Give
Set point 2
the value Sp2 = 4
°
C from Fig. 15.
At the same time, set Neutral zone = 3
°
C and Prop. band = 10
°
C as starting points. The system is now
adjusted to the desired function. The picture will now look like this:
The
Actual Setpoint
shows the regulating value of the inlet temperature at that particular moment. If the
outside temperature is 30
°
C, this value must be 4
°
C. If the outside temperature is 0
°
C, the value must
be 12
°
C. The outside temperature can be seen in % of the measuring range in the picture
Control val-
ues/Capacity/Values
.
40
30
20
10
-10
4
2
6
10
12
8
14
Sp 1
Sp2
T
out
T
inlet