Engineering manual - UniSAB III 1.10.8
001930 en 2021.06
123/346
Compressor control and surveillance
Stopping sequence
At normal stop (to avoid back-spin) the SSTV valve is closed for the time stated in the timer
SSTV delay
before the compressor is stopped. The default setting is 40 seconds but it is adjustable between 0 and
60 seconds.
Note:
The SSTV timer starts counting after the
stop delay
timer has run out. This means that the com-
pressor will not stop immediately even though the stop key is pressed or the instant stop digital input is
removed.
After compressor stop the SSTV valve is kept closed for 60 seconds, not adjustable, and the cooling fan
will have a stop delay of 10 seconds. The stop delay for the cooling fan can be set in the
Timers/Motor
fan/Run timer SP
menu.
At shutdown the frequency converter is stopped immediately and the SSTV valve is closed immediately.
Vi ratio regulation
UniSAB III regulates the Vi ratio in three steps according to the actual pressure ratio. Before switching
from one Vi step to another, the actual Vi ratio for the compressor must have been present for at least
the time indicated in timer 34
Vi-pause
(60 seconds). Otherwise, the change of the Vi step will be
cancelled.
Vi ratio .../Capacity/Vi ratio
Vi low range setting
Vi high range setting
Dig. output 12 (Vi)
1.9
2.6
Off
3.2
4.8
On
3.3.25
Oil charging, manually (screw compressors)
Oil cannot be charged when UniSAB III is in
Stopped
mode. If the compressor is fitted with an oil pump
for oil charging, it can be started the following way: Select
Setup/Timers/Oil Charging
and the following
picture appears:
Place the cursor on
Run timer
, press
to enter the parameter change field, use
and
to adjust the
value and press
to store the value.
Move the cursor to
Start oil pump
. Press
, select
Yes
with
and press
to store the value.
The pump will now start and run for the time set.
For SAB 202, SAB Mk 3 and VMY Mk 3 compressors a
Watch the oil pressure
alarm will be issued while
the oil pump is in manual operation for oil charging. If the pump should stop before time expiry, select
No
under
Start oil pump
.
Note:
As from 2001 SAB 128/163 Mk 3 and SAB 202 are no longer as standard fitted with a valve for ex-
ternal connection to the oil pump suction side. It is therefore not possible to charge oil with the unit oil
pump.