Engineering manual - UniSAB III 1.10.8
001930 en 2021.06
271/346
7.6
Electrical slide systems (certain screw compressors)
The built-in capacity slide position transmitter must be adjusted correctly to ensure safe and reliable
slide control. This adjustment must always be carried out as described in
Afterwards, the capacity signal must be adjusted by software as described in
.
7.6.1
Manual slide positioning
Contrary to hydraulic slides, the electrical capacity slide can be positioned manually for testing. This is
useful when performing transmitter adjustment and software adjustment. Select
Setup/Compr. Control
Mode = Stop
and then
Setup/Configuration/Calibrate/Position
.
The following picture will appear:
While this picture is open (and UniSAB III is still in
Stop
mode) the capacity slide can be moved by
means of
/CAP. UP and
/CAP. DOWN.
Note that when reaching the end stop, the shutdown
Capacity error
will be displayed after two seconds.
Release the button at once and reset the shutdown.
7.6.2
Transmitter adjustment
The capacity transmitter is fitted with a single calibration button surrounded by a green and a red LED
as shown in Fig. 42.
Fig. 42: Capacity transmitter
F2
F3
LED position
(Green)
Calibration
push button
LED-working
(Red)
Normally, not visible
For calibration
remove cover