Engineering manual - UniSAB III 1.10.8
001930 en 2021.06
107/346
Compressor control and surveillance
3.3.11
FV 24/26 with oil pump
The compressors FV 24 and FV 26 are small frequency-regulated screw compressors, i.e. the mounted
slide is only used during start and stop.
The electrical oil pump is used for prelubrication and to maintain a minimum oil pressure during opera-
tion. The pump is started and stopped in accordance with the compressor differential pressure (dis-
charge pressure - suction pressure) during operation.
The difference is set in the picture
Oil/Pressure/Control
whereupon
Set point 1
and
Set point 2
will
appear.
Normal setting for FV 24/26:
Set point 1 = 2.5 bar
Set point 2 = 4.0 bar
Adjust set points as described in subsection 3.3.5
Starting sequence
Once the compressor has received permission to start, the oil pump will start pumping oil into the com-
pressor lubrication system.
The oil flow switch must be activated within 45 seconds to avoid shutdown.
When the oil flow switch is activated, the solenoid valve (capacity slide down) will be open for 15 sec-
onds and the electrical fan will start. The frequency converter will then receive a signal to start. Speed is
increased to 1000 rpm in 10 seconds.
The pump will operate for a minimum of 60 seconds and will stop if the differential pressure is higher
than
Set point 2
as described above.
Alarm surveillance
During start the following alarms are delayed:
Low oil pressure
45 sec.
High filter diff. pressure
300 sec.
Low superheat
300 sec.
High superheat
300 sec.
Low/high oil temperature
300 sec.
See also section
.
3.3.12
SV 24/26 with oil pump
The compressors SV 24 and SV 26 are small slide regulated screw compressors.
The electrical oil pump is used for prelubrication and to maintain a minimum oil pressure during
operation.
The pump is started and stopped in accordance with the compressor differential pressure (discharge
pressure - suction pressure) during operation.
The difference is set in the picture
Oil/Pressure/Control
whereupon
Set point 1
and
Set point 2
will
appear.
Normal setting for SV24/26:
Set point 1 = 2.5 bar
Set point 2 = 4.0 bar
Adjust set points as described in subsection 3.3.5