Engineering manual - UniSAB III 1.10.8
260/346
001930 en 2021.06
7.3
Temperature sensors (process out temperature)
The only temperature sensor which can be calibrated is the
Process out temperature
sensor. Place the
cursor on
Process Out temp. (Brine)
and press the
key once. The following picture will appear:
The
Process Out temp.
value is the immediate value measured by the sensor. If a test measuring with a
precision thermometer shows e.g. 18.7
°
C at the sensor, adjustment can be made. Place the cursor on
Proc. out temp Adj
and change the value to -0.2
°
C.
Process Out temp.
will now be 18.7
°
C (18.9-0.2)
and adjustment is complete.
7.4
Motor
7.4.1
Motor frequency signal
When compressor capacity is regulated wholly or partly by changes in the motor speed, the motor fre-
quency signal from the frequency converter can be calibrated in this menu:
7.4.2
Motor current
The reading of motor current can be calibrated as described in subsection
Содержание SABROE Unisab III Control