Engineering manual - UniSAB III 1.10.8
154/346
001930 en 2021.06
Compressor control and surveillance
3.8.7
Configuration
To obtain a correct calculation of the zero point it is important that the compressor type and swept vol-
ume have been entered correctly.
The swept volume of the compressor is determined on the basis of:
•
Compressor type
•
rpm (50/60 Hz)
•
Male/female rotor
On SAB 202, UniSAB III will automatically enter a swept volume value corresponding to the S type with
male rotor and a two-pole 50 Hz motor (1229 m3/h). The correct swept volume must be based on the
number of revolutions of the compressor (50/60 Hz supply) and whether the compressor has male or fe-
male rotor drive:
SAB 202 SM/ 50 Hz, swept volume = 1229 m3/h
SAB 202 SM/ 60 Hz, swept volume = 1475 m3/h
SAB 202 SF/ 50 Hz, swept volume = 1843 m3/h
SAB 202 SF/ 60 Hz, swept volume = 2212 m3/h
SAB 202 LM/ 50 Hz, swept volume = 1590 m3/h
SAB 202 LM/ 60 Hz, swept volume = 1908 m3/h
SAB 202 LF/ 50 Hz, swept volume = 2385 m3/h
SAB 202 LF/ 60 Hz, swept volume = 2862 m3/h
The nominal swept volume at 50 Hz is stated on the compressor name plate.
As already mentioned, there are two configuration points in the picture
Setup/Configuration/Compressor
block
:
Mechanical zero No [/Yes]
Manual zero 0.0%
Only if the compressor has a built-in spacer block and automatic Vi regulation, should the
Mechanical
zero
be set to
Yes
. In all other cases
Mechanical zero
must be set to
No
. See subsection
To make a manual setting of the zero point, enter a zero point between 0-40% of maximum capacity
slide travel in
Manual zero
0.0%.
See the subsection
3.8.4 Manual setting of new zero point (all screw compressors)
3.8.8
Zero pos. picture
The current calculated zero point value as well as any manually set zero point value can be read in the
Diagnosis
picture:
Service/Diagnose/Software/Zero Cap. Position
.
The following calculated capacity values can also be read in the
Diagnosis
picture:
•
Relative Cap. Vi
capacity calculated relative to Vi slide position
•
Relative Cap. MZ
capacity calculated relative to manual zero and ViI slide position
Содержание SABROE Unisab III Control
Страница 1: ...UniSAB III control Version 1 10 8 Engineering manual EN...
Страница 2: ......
Страница 347: ......