Compressor control and surveillance
Alarm surveillance
During start the following alarms are delayed:
Low oil pressure
45 sec.
High filter diff. pressure
300 sec.
Low superheat
300 sec.
High superheat
300 sec.
Low/high oil temperature
300 sec.
3.3.6
SAB 128HR and 163HR with oil pump
The compressors SAB 128 HR and SAB 163 HR are frequency-regulated screw compressors, i.e. the
capacity slide is fixed in maximum position and cannot be moved.
The electric oil pump is used for prelubrication and to maintain a minimum oil pressure during operation.
The pump is started and stopped in accordance with the compressor differential pressure (discharge
pressure - suction pressure) during operation.
The difference is set in the picture
Oil/Pressure/Control
whereupon
Set point 1
and
Set point 2
will
appear.
Normal setting for SAB 128/163 HR:
Set point 1 = 2.5 bar
Set point 2 = 4.0 bar
Adjust set points as described in subsection 3.3.5
Starting sequence
Once the compressor has received permission to start, the oil pump starts and oil is pumped into the
compressor lubrication system.
The oil flow switch must be activated within 600 seconds to avoid shutdown.
When the oil flow switch is activated, the solenoid valve (capacity slide down) will be open for 15 sec-
onds and the electric fan will start. The frequency converter will receive a signal to start.
Speed is increased to 1000 rpm in 10 seconds.
The pump will operate for a minimum of 60 seconds and stop if the differential pressure is higher than
Set point 2
as described above.
Alarm surveillance
During start the following alarms are delayed:
See also section
Low oil pressure
45 sec.
High filter diff. pressure
300 sec.
Low superheat
300 sec.
High superheat
300 sec.
Low/high oil temperature
300 sec.