Whenever the emergency stop is activated during operation, the alarm text
Compr. motor error
will ap-
pear in the display. Before the compressor can be restarted, deactivate the alarm by means of the
/RESET key and release the emergency stop.
Note:
If UniSAB III is set at
Remote
or
Auto
, the compressor will restart automatically.
Technical data
Power supply
Nominal VAC
Hz
85-250
47-63
Consumption
32 VA
Main supply terminals
2.5 mm
2
rated cross section
Ambient temperature
0-55
°
C (during operation)
Humidity
10-90% relative humidity (not condensing)
Tightness
IP 54
F4