Engineering manual - UniSAB III 1.10.8
244/346
001930 en 2021.06
An alarm is issued if the timer runs out. See subsection
2.2.33 Low oil circuit pressure alarm
for more
details about this alarm.
38. Oil cir.shutd. (Low oil circuit pressure shutdown)
For SGC compressors (SAB 120
→
151, SAB 193
→
355, SAB 193 H
→
355 H, SAB 157 HR and SAB 273
S)
This timer starts if the difference in pressure between oil pressure and discharge pressure exceeds 2.0
bar.
A shutdown is issued if the timer runs out. See subsection
2.2.34 Low oil circuit pressure shutdown
for
more details about this shutdown.
39. SSSTV Delay (suction strainer stop throttle valve)
For SABflex and SABCube compressors only.
At normal stop (to avoid back-spin) the SSSTV valve is closed for the time stated in the timer SSSTV de-
lay before the compressor is stopped. The default setting is 40 seconds but it is adjustable between 20
and 60 seconds.
Note:
The SSSTV timer starts counting after the stop timer has run out. This means that the compressor
will not stop immediately, even though the stop key is pressed or the instant stop digital input is
removed.
40. Max. start-up time
For SABflex and SABCube compressors only.
During start-up the speed for a SAB 109-159 may be limited to 1,000 [rpm], if the internal suction pres-
sure is too high or the oil pressure is too low. The start-up limiter will only be active at compressor start-
up and it can maximum be active for the time set in timer “Max. start-up time”.
If the start-up limiter is still active when the “Max. start-up time” timer runs out, a shutdown is given and
the compressor is stopped.
41. Oil return open
For chiller use only.
This timer controls the open time for the oil return valve draining the oil separator.
42. Oil return close
For chiller use only.
This timer controls the closed time for the oil return valve draining the oil separator.
43. By-pass start
For chiller use only.
This timer controls that, at compressor start-up, a start unload valve opens for the set time.
44. Flow evaporator
For chiller use only.
After the float switch has become low, this timer delays the shutdown
No evaporator flow
.