Engineering manual - UniSAB III 1.10.8
74/346
001930 en 2021.06
Compressor control and surveillance
If the regulator for a long period of time seems to hunt, increase the
T. int.
to e. g. 100-200 sec. If the
hunting stops, reduce the
T. int
. until the system starts hunting again. Now increase the
T. int.
to the last
applicable value.
Usually it will never be necessary to change the
T. diff.
to a value different than 0 sec. However, in spe-
cial cases where the compressor is part of a process plant, e.g. in petrochemical plants, it may be nec-
essary to use another value than 0 sec. This will only be necessary if the process requires a very fast
regulation upwards or downwards to avoid that the suction pressure removes itself too far from the set
point.