Engineering manual - UniSAB III 1.10.8
001930 en 2021.06
167/346
When the alarm is acknowledged by a Johnson Controls service technician (JCI) with Supervisor pass-
word after finished service the service counter
Next main service C or D
and the start counter
Starts
since main
will be reset to zero. No matter if it is at 1000 hours, 200 hours or 0 hours before service.
Last service alarm ack.
and
Ack time
will indicate by whom and when the last service alarm was ac-
knowledged, e.g.:
Last serv. alm. ack.
None, User, JCI
Ack. time:
18-02-2011
The date field is 00-00-00 if status is None
Date, time and the service information (i.e. service name, service status, calculated service interval in
hours and hour counter) will be saved in the event list. Service status will be
User
if the service alarm is
acknowledged by the customer and
JCI
if the service alarm is acknowledged by a Johnson Controls
service engineer.