Engineering manual - UniSAB III 1.10.8
88/346
001930 en 2021.06
Compressor control and surveillance
Example 2:
On a heat pump unit the inlet temperature must be corrected by the outside temperature.
•
If the outside temperature is +30°C, the inlet temperature must be +40
°
C.
•
If the outside temperature is -10°C, the inlet temperature must be +65
°
C.
In the menu
Setup/Compr. Control
, adjust
Control on
to
Hotwater
and
Climate compensation
to
Yes
. Se-
lect an outside sensor in the range -10 - +30
°
C.
Fig. 16: Climate compensation, example 2
The settings in the drawing are:
Sp1 = 65
°
C at To = -10
°
C and
Sp2 = 40
°
C at To = 30
°
C.
Note that
Sp1
refer to the lowest and that
Sp2
refer to the highest outside temperature.
The straight line indicates the inlet temperature variation under influence of the outside temperature.
Select the menu
Control values/Process temp./Process out temp./Control
and go down to
Set point 1
and
Set point
.
Give
Set point 1
the value
Sp1
= 65
°
C from Fig. 14.
Give
Set point 2
the value
Sp2
= 40
°
C from Fig. 16.
At the same time, set
Neutral zone
= 3
°
C and
Prop. band
= 10
°
C as starting points. The system is now
adjusted to the desired function.
-20
10
-10
20
30
40
20
30
40
50
60
70
10
80
Sp 1
T out
T inlet
Sp 2