Engineering manual - UniSAB III 1.10.8
82/346
001930 en 2021.06
Compressor control and surveillance
3.1.10
User input regulator (Ext. input)
In addition to the above mentioned regulators the
User input
regulator can also be used. To do so, con-
nect a 4-20 mA sensor (pressure, temperature or other) to the UniSAB III input named
User input 1
(Ex-
ternal set point). When selecting 4-20 mA input in the menu
Setup/Configuration/External input
, the
following picture will appear:
The signal must be scaled to fit the sensor measuring range. Ex.: A temperature sensor of -30
°
C to +20
°
C is used.
Move the cursor to 4 mA, press
and change the value to -30. Move the cursor to 20 mA, press
and change the value +20.
Move the cursor to second line, press
and select
Ext. input signal
with
or
. Finish by pressing
. The picture will now look like this:
Each measuring signal can be scaled in accordance with the transducer measuring range.
In the menu
Setup/Compr. Control
, select one of the following in the
Control on
line:
Ext. cool
If selecting this function, the compressor will regulate the capacity upwards in case of increasing meas-
uring value.
Ext. heat
If selecting this function, the compressor will regulate the capacity upwards in case of decreasing meas-
uring value.
Now select picture
Control values/User/User input 1/Control
. Go to the bottom of the picture with
where the set values of the regulator are positioned. These can be set by pressing
followed by
or
.