Goodrive300-01A series VFD for air compressor
Function code description
-48-
Function
code
Name
Description
Default Modify
P07.15
High bit of power
consumption of the
VFD
0
–65535 kWh (*1000)
●
P07.16
Low bit of power
consumption of the
VFD
0.0
–999.9 kWh
●
P07.17
VFD model
0: G type
1: P type
●
P07.18
Rated VFD power
0.4
–3000.0kW
●
P07.19
Rated VFD voltage
50
–1200V
●
P07.20
Rated VFD current
0.1
–6000.0A
●
P07.21
Factory barcode 1
0x0000
–0xFFFF
●
P07.22
Factory barcode 2
0x0000
–0xFFFF
●
P07.23
Factory barcode 3
0x0000
–0xFFFF
●
P07.24
Factory barcode 4
0x0000
–0xFFFF
●
P07.25
Factory barcode 5
0x0000
–0xFFFF
●
P07.26
Factory barcode 6
0x0000
–0xFFFF
●
P07.27
Type of present fault 0: No fault
1: Inverter unit U phase protection (OUt1)
2: Inverter unit V phase protection (OUt2)
3: Inverter unit W phase protection (OUt3)
4: Overcurrent at acceleration (OC1)
5: Overcurrent at deceleration (OC2)
6: Overcurrent at constant speed (OC3)
7: Overvoltage at acceleration (OV1)
8: Overvoltage at deceleration (OV2)
9: Overvoltage at constant speed (OV3)
10: Bus undervoltage fault (UV)
11: Motor overload (OL1)
12: VFD overload (OL2)
13: Phase loss on input side (SPI)
14: Phase loss on output side (SPO)
15: Rectifier module overheat (OH1)
16: Inverter module overheat (OH2)
17: External fault (EF)
18: 485 communication fault (CE)
19: Current detection fault (ItE)
20: Motor autotuning fault (tE)
●
P07.28
Type of the last fault
●
P07.29
Type of the last but one
fault
●
P07.30
Type of the last but two
fault
●
P07.31
Type of the last but
three fault
●
P07.32
Type of the last but
four fault
●
Содержание Goodrive300-01A Series