Goodrive300-01A series VFD for air compressor
Function code description
-79-
Function
code
Name
Description
Default Modify
P21.06
Calibration coefficient
of C phase current of
the fan
100.0%
○
P21.07
User-defined fault
action selection 1
Ones: Motor overload (OL1)
0: Coast to stop
1: Runs at alternative frequency of P21.10
Tens: Electronic overload (OL3)
0: Process as per P11.08
1: Run at alternative frequency of P21.10
Hundreds: Rectifier module overheat (OH1)
0: Coast to stop
1: Run at alternative frequency of P21.10
Thousands: Inverter module overheat fault
(OH2)
0: Coast to stop
1: Run at alternative frequency of P21.10
0x0000
○
P21.08
User-defined fault
action selection 2
Ones: Underload (LL)
0: Process as per P11.08
1: Run at alternative frequency of P21.10
Tens: External fault 1 signal
0: Coast to stop
1: Run at alternative frequency of P21.10
Hundreds: External fault 2 signal
0: Coast to stop
1: Run at alternative frequency of P21.10
Thousands: Reserved
0: Coast to stop
1: Run at alternative frequency of P21.10
0x0000
○
P21.09
User-defined fault
action selection 3
Ones: 485 communication fault (CE)
0: Coast to stop
1: Run at alternative frequency of P21.10
Tens: EEPROM operation fault (EEP)
0: Coast to stop
1: Run at alternative frequency of P21.10
Hundreds:
Current
overload
of
power-frequency fan (OLF)
0: Coast to stop
1: Run at alternative frequency of P21.10
Thousands: 3PH current imbalance of
0x0000
○