Goodrive300-01A series VFD for air compressor
Fault information and troubleshooting
-92-
Fault
code
Fault type
Possible cause
Solution
Motor parameters are set
improperly.
The deviation between the
parameters obtained from
autotuning and the
standard parameter is
huge.
Autotuning timeout.
nameplate parameters
correctly.
Empty the motor load and
identify again.
Check the motor wiring and
parameter setup.
Check whether upper limit
frequency is larger than 2/3
of the rated frequency.
EEP
[21] EEPROM
operation fault
Error occurred to the
writing/reading of control
parameters.
EEPROM damaged.
Press STOP/RST to reset.
Replace the main control
board.
PIDE
[22] PID feedback
offline fault
PID feedback offline.
PID feedback source
disappears
Check PID feedback signal
wire.
Check PID feedback source
END
[24] Running time is
up
The actual running time of
the VFD is larger than the
internally set time.
Ask supplier for help.
Adjust the set running time.
OL3
[25] Electronic
overload fault
The VFD reports overload
pre-alarm according to the
set value.
Check the load and
overload pre-alarm
threshold.
PCE
[26] Keypad
communication fault
Keypad wire is poorly
contacted or disconnected.
Keypad wire is too long
and suffers strong
interference.
Keypad or communication
circuit is faulty.
Check the keypad wire and
confirm whether fault exists.
Check the environment and
rule out interference
source.
Replace the hardware, and
ask for maintenance
service.
UPE
[27] Parameter
upload error
Keypad line is poorly
contacted or disconnected.
Keypad wire is too long or
suffers strong interference.
Keypad or mainboard
communication circuit is
faulty.
Check the environment and
rule out the interference
source.
Replace the hardware, ask
for maintenance service.
Replace the hardware, ask
for maintenance service.