Goodrive300-01A series VFD for air compressor
Function code description
-67-
Function
code
Name
Description
Default Modify
0: Invalid
1: Automatic sleep mode
2: Manual sleep mode
Note:
When automatic sleep function is valid
and unloading conditions are fulfilled, the VFD
decelerates to P18.12 [no-load running
frequency], and then, if discharge pressure is
larger than P18.06 [loading pressure] during
the time set by P18.13, the VFD will
decelerate to P01.15 [stop speed] and then
coast to stop to enter sleep stage. If the
discharge pressure is less than loading
pressure during P18.13, the VFD will perform
loaded running again, and pressure PID will
regulate accordingly.
Manual sleep:
Conduct manual sleep
through
the
touch
screen
or
other
communication methods.
P18.02
Loading/unloading
mode
0: Automatic;
1: Manual
When setting to manual state, after air
compressor
starts,
loading/unloading
manually; when setting to automatic mode,
the
air
compressor
loads/unloads
automatically after starting.
0
○
P18.03
Temperature sensor
channel
0: Machine head temperature PT 1, auxiliary
temperature PT2
1: Machine head temperature PT 2, auxiliary
temperature PT1
2: Temperature display in normal VFD mode
(P18.00=0) (machine head temperature PT1,
auxiliary temperature PT2)
1
◎
P18.04
Upper limit of pressure
sensor P1
0.00
–20.00 Mpa
Related to the actual range of pressure
sensor, the corresponding voltage of P18.04
is P05.34.
Note: When restoring to default value, this
value stays in currently set value.
1.60Mpa
◎
P18.05
Unloading pressure Under automatic loading/unloading mode, 0.80Mpa
○