Goodrive300-01A series VFD for air compressor
Function code description
-52-
Function
code
Name
Description
Default Modify
used in the calculation.
1: Enable
It is applicable to the embedded/
surface-mounted
synchronous
motors.
P02.21 (Direct-axis inductance of SM 1) is
used in the calculation.
Note:
You can disable or enable the
optimization mode according to the motor at
the scene.
P08.28 Auto fault reset count During the automatic reset period, the fault
will not be reported externally, only the keypad
TRIP indicator blinks, and P17.39 shows the
warning code. The automatic fault reset
function is enabled for these faults, such as
OUt1, OUt2, Out3, OL1, OL2, OH1, OH2, EF,
CE, ItE, tE, EEP, END, PCE, UPE, DNE,
ETH1, ETH2, PSF, etc. Fault codes will be
reported immediately when these types of
faults occur.
Setting range of P08.28: 0
–10
Setting range of P08.29: 0.1
–3600.0s
5
○
P08.29
Auto fault reset interval
setting
5.0
○
P08.30
Frequency decrease
ratio in drop control
0.00
–50.00Hz
0.00Hz
○
P08.32
FDT1 electrical level
detection value
0.00
–P00.03 (max. output frequency)
50.00Hz
○
P08.33
FDT1 lagging
detection value
-100.0
–100.0% (FDT1 electrical level)
5.0%
○
P08.34
FDT2 electrical level
detection value
0.00
–P00.03 (max. output frequency)
50.00Hz
○
P08.35
FDT2 lagging
detection value
-100.0
–100.0% (FDT2 electrical level)
5.0%
○
P08.36
Detection value for
frequency being
reached
0.0
–P00.03 (max. output frequency)
0.00Hz
○
P08.39
Cooling fan running
mode
0: Common running mode: Do not run during
sleep.
1: The fan keeps running after being
powered on
2: Temperature control: The fan turns on when
0
○