Goodrive300-01A series VFD for air compressor
Fault information and troubleshooting
-96-
P19.13
State type
Possible cause
Solution
not select current signal.
BIT13=1
Temperature signal
fault
PT100 sensor is
disconnected.
Check whether the wiring of
PT100 is normal.
Check whether temperature
detection sensor is abnormal.
Temperature detection input
circuit is abnormal.
BIT14=1
Low-temperature
protection pre-alarm
The actual temperature
detected by PT1 is less
than the low
temperature protection
threshold set by
P18.21.
Temperature detection sensor
is abnormal.
Temperature detection input
circuit is abnormal.
Actual temperature is too low,
and low temperature
pre-alarm is reported
accordingly, and therefore the
air compressor cannot start.
P19.14
State type
Possible cause
Solution
BIT0=1
Part 1 needs
maintenance
The running time of part
1 exceeds the time set
by P19.00.
Carry out maintenance after
stop
BIT1=1
Part 2 needs
maintenance
The running time of part
2 exceeds the time set
by P19.01.
Carry out maintenance after
stop
BIT2=1
Part 3 needs
maintenance
The running time of part
3 exceeds the time set
by P19.02.
Carry out maintenance after
stop
BIT3=1
Part 4 needs
maintenance
The running time of part
4 exceeds the time set
by P19.03.
Carry out maintenance after
stop
BIT4=1
Part 5 needs
maintenance
The running time of part
5 exceeds the time set
by P19.04.
Carry out maintenance after
stop
BIT5=1
Auxiliary pressure
signal fault
The actual voltage
detected by P2 is less
than 1V.
Pressure detection sensor is
abnormal.
Pressure detection input P2
signal wire is disconnected.
BIT6=1
Auxiliary temperature
signal fault
PT100 sensor is
disconnected.
Check whether the wiring of
PT100 is normal.