Goodrive300-01A series VFD for air compressor
Function code description
-42-
Function
code
Name
Description
Default Modify
P05.04
S4 terminal function
selection
6: Coast to stop
7: Fault reset
8: Running pause
9: External fault input
10
–24: Reserved
25: PID control pause
26
–39: Reserved
40: Zero out power consumption
41: Maintain power consumption
42: Air filter blockage signal
43: Oil filter blockage signal
44: Separator blockage signal
45: Precision splitter blockage signal
46: External fault 1 (motor overtemperature)
47: External fault 2
48: Reserved
49: Solenoid valve control signal
50: Cooling fan control signal of main motor
51
–63: Reserved
0
◎
P05.05
S5 terminal function
selection
0
◎
P05.06
Reserved
◎
P05.10
Input terminal polarity
selection
This function code is used to set the input
terminal polarity.
When the bit is set to 0, input terminal polarity
is positive;
When the bit is set to 1, input terminal polarity
is negative.
BIT8
BIT7
BIT6
BIT5
Reserved
BIT4
BIT3
BIT2
BIT1
BIT0
S5
S4
S3
S2
S1
Setting range: 0x000
–0x1FF
0x000
○
P05.11
Digital filter time
0.000
–1.000s
0.200s
○
P05.14
S1 terminal switch-on
delay
0.000
–50.000s
0.000s
○
P05.15
S1 terminal switch-off
delay
0.000
–50.000s
0.000s
○
P05.16
S2 terminal switch-on
delay
0.000
–50.000s
0.000s
○