Goodrive300-01A series VFD for air compressor
Function code description
-78-
Function
code
Name
Description
Default Modify
P19.22
Input power phase
sequence state
If the VFD enables phase sequence detection
and input phase loss hardware protection,
corresponding fault will be reported when
negative sequence and any phase loss
occurs; otherwise, fault will not be reported.
0: Positive sequence
1: Negative sequence
2: R phase loss
3: S phase loss
4: T phase loss
0
●
P19.23
State of phase
sequence detection flat
cable
0: Normal, indicating the flat cable is plugged
in properly
1: Abnormal, indicating the flat cable is not
plugged in
0
●
P21 group Power-frequency fan protection
Function
code
Name
Description
Default Modify
P21.00
Rated fan current
0.0
–40.0A
This function code is related to current
detection and overload protection function of
power-frequency fan.
Set to 0 will disable this function.
0.0A
○
P21.01
Current transformation
ratio of the fan
1.0
–4000.0
200
(
≤15kW);
1000
(
≥18.5k
W)
○
P21.03
Current imbalance
coefficient
1.00
–3.00
Among the current of three phases of the fan,
if the ratio between max. current and min.
current is larger than P21.03, the VFD
displays fan current imbalance fault.
3.0
○
P21.04
Calibration coefficient
of A phase current of
the fan
0.0
–150.0%
Actual current=display current*current
calibration coefficient
Note:
When restoring to default values, this
value will stay in currently set value.
100.0%
○
P21.05
Calibration coefficient
of B phase current of
the fan
100.0%
○