Goodrive300-01A series VFD for air compressor
External optional accessories
-137-
Step 4 Enter the commissioning mode. Run the master and fan in jogging mode to check the motor
rotation direction.
Step 5 Adjust user parameters, factory parameters, and maintenance parameters according to the
manual.
During commissioning, if a signal exception occurs, check VFD information to view the signal status
and handle the exception.
B.1.7.2 Date and time display
Generally, the date and time in the format of
AA.BB aa:bb:cc
is displayed in the upper left corner of
the keypad interface. In the format,
AA
indicates month,
BB
indicates date,
aa
indicates hour,
bb
indicates minute, and
cc
indicates second. For example, the "03.17 16:02:35" in the following figure
indicates the current time is 16:02:35 on March 17.
Note
: The real-time clock function can be used properly only when batteries are available. The
battery compartment is located on the back of the keypad. You only need to remove the lid to check
whether batteries are available.
03.17 16:02:35
Set
Alarm
Menu
Workspace
Output Freq
P17.01
Hz
0.00
Present Pressure
P19.11
0.00
25
Mpa
Present Temp
P19.12
℃
Ready
B.1.7.3 Password setting
The controller provides multi-level password and permission management. The mapping between
passwords and permissions is as follows:
User password: able to modify user password and clear fault records.
Administrator password: able to modify maintenance parameters, protection parameters, master
parameters, and fan parameters, in addition to the permissions with a user password.
Factory password: able to modify all parameters.
Super factory password: able to modify all parameters.
Passwords are changeable. To change a password, enter the password correctly, enter a new
password, and then re-enter the new password for confirmation. The password can be changed
successfully only when no errors are made.