Goodrive300-01A series VFD for air compressor
Fault information and troubleshooting
-91-
Fault
code
Fault type
Possible cause
Solution
transients
OL2
[12] VFD overload
Acceleration is too fast.
The motor is restarted
during rotating.
The grid voltage is too low.
The load is too large.
Increase acceleration time.
Restart the motor after stop.
Check grid voltage.
Adopt the VFD with a larger
power.
Select a proper motor.
SPI
[13] Phase loss on
input side
Phase loss or fluctuation
occurs to input R, S and T.
Check input power.
Check installation wiring.
SPO
[14] Phase loss on
output side
Phase loss output occurs
to U, V and W (or serious
3PH imbalance occurs to
the load).
Check the output wiring.
Check the motor and cable.
OH1
[15] Overheat of
rectifier module
Air duct blocked or fan
damaged.
Ambient temperature is too
high.
Long-time overload
running.
Ventilate the air duct or
replace the fan.
Lower down the ambient
temperature.
OH2
[16] Overheat of
inverter module
EF
[17] External fault
S external fault input
terminal acts.
Check external equipment
input.
CE
[18] 485
communication fault
Baud rate is set improperly.
Communication line fault.
Communication address
error.
Communication suffers
strong interference.
Set proper baud rate.
Check the wiring of
communication interface.
Check the wiring of
communication interfaces.
Set correct communication
address.
Replace or change the
wiring to improve
anti-interference capacity.
ItE
[19] Current
detection fault
Poor contact of controller
board connector.
Hall components are
damaged.
Amplifying circuit is
abnormal.
Check the connector and
re-plug wires.
Replace the hall.
Replace the main control
board.
tE
[20] Motor
autotuning fault
Motor capacity does not
match VFD capacity.
Change the VFD model.
Set motor type and