Goodrive300-01A series VFD for air compressor
Wiring instruction
-20-
Category
Sign
Name
Function
Ib
B-phase current input of
the fan
3. Input impedance:
50Ω
Note:
See
Appendix C
for model
selection of current transformer.
Ic
C-phase current input of
the fan
Jumper terminal
J7
P1-Analog signal
selection terminal
I corresponds to current signal, V
corresponds to voltage signal, and the
default is current input signal.
J8
P2-Analog signal
selection terminal
I corresponds to current signal, V
corresponds to voltage signal, and the
default is current input signal.
J2
AO1 analog output signal
selection terminal
I corresponds to current signal, V
corresponds to voltage signal, and the
default is voltage output signal.
J5
Connection terminal of
485 communication
terminal resistor
ON corresponds to terminal resistor. ON
is not connected to terminal resistor by
default.
J6
Short-connect terminal
between PE and GND
No short connection by default
J9
Internal/external power
selection terminal
PW is connected to +24V by default. See
Figure 3-19 and Figure 3-20.
J10
PE/CGND selection
terminal
RS485
communication
adopts
non-isolation mode, and CN7-10 is short
connected to PE by default. See Figure
CGND
J10
to controller
PE
CN7-10
GND
+24V
485-
485+
/PE
CGND
--twisted pair
--shielded cable
PE
H9
Figure 3-18 485 communication wiring diagram (non-isolation mode)