Goodrive300-01A series VFD for air compressor
Product overview
-6-
Category
Function
Specification
Digital output
Two relay outputs (NO) 250VAC/3A; one
convertible relay output 250VAC/3A
Fault protection function
Over 30 kinds of fault protection functions:
overcurrent,
overvoltage,
undervoltage,
overtemperature, phase loss, overload, fan
current imbalance, etc.
Fan protection function
Overload protection: 1 min at 120% overload;
48s at 130% overload; 24s at 150% overload;
8s at 160% overload; 5s at 200% overload; 1s
at 300% overload
Current imbalance protection: when any two
phases differ from each other by 60
–75%, stop
at fault, action time
≤5s
Output short-circuit protection: the protection
can be implemented by using the internal fuse
(applicable to single VFD integrated machine
only)
Output
short-to-ground
protection:
the
protection can be implemented by using the
internal fuse (applicable to single VFD
integrated machine only)
Solenoid valve port protection
220V/110V output short-circuit protection: the
protection can be implemented by using the
internal fuse (applicable to single VFD
integrated machine only)
485 communication
One 485 communication (three terminal
interfaces)
Others
Installation mode
Wall installation, flange installation
Temperature of running
environment
-10
–50°C, derating is required if the
temperature exceeds 40°C; derate by 1% for
every increased 1°C
Protection level
IP20
Pollution level
Level 2
Cooling mode
Forced-air cooling
DC reactor
DC reactors are optional parts for 7.5
–11kW
VFD models and can be built into the models;
DC reactors have been built into 15
–110kW
models as standard configuration;
DC reactors are optional parts for 132
–315kW