Goodrive300-01A series VFD for air compressor
Fault information and troubleshooting
-93-
Fault
code
Fault type
Possible cause
Solution
DNE
[28] Parameter
download error
Keypad line is poorly
contacted or disconnected.
Keypad wire is too long or
suffers strong interference.
Storage data in the keypad
is wrong.
Check the environment and
rule out the interference
source.
Replace the hardware, ask
for maintenance service.
Re-copy the data in the
keypad.
ETH1
[32] To-ground short
circuit fault 1
VFD output is short
circuited to ground.
Current detection circuit is
faulty.
Actual motor power setup
differs sharply from the
VFD power.
Check whether motor wiring
is normal/motor is short
circuited to ground.
Replace the hall.
Replace main control
board/drive board.
Reset correct motor
parameters.
ETH2
[33] To-ground short
circuit fault 2
dEu
[34] Speed deviation
fault
Load is too heavy or stall.
Check the load and ensure
it is normal, increase the
detection time.
Check whether control
parameters are proper.
STo
[35] Maladjustment
fault
Control parameters of
synchronous motor is set
improperly.
Autotuning parameters are
inaccurate.
VFD is not connected to
the motor.
Check the load and ensure
the load is normal.
Check whether control
parameters are set
correctly.
Increase maladjustment
detection time.
LL
[36] Electronic
underload fault
The VFD reports underload
pre-alarm according to the
set value.
Detect the load and
underload pre-alarm
threshold.
PSF
[38] Phase
sequence fault
The phase sequence on
power input side is
negative.
Swop any two of the power
input cables.
SPOF
[39] 3PH current
imbalance of
power-frequency fan
Phase loss occurs to 3PH
wiring of the fan.
Stator winding of 3PH of
the fan is abnormal.
Poor grid quality.
Check whether the fan is
disconnected or poorly
contacted.
Measure whether the 3PH
winding impedance of the
fan is balanced.