Goodrive300-01A series VFD for air compressor
Function code description
-62-
Function
code
Name
Description
Default Modify
P15.01
Auxiliary pressure
start protection
threshold
0.00
–20.00MPa
The VFD cannot start if present auxiliary
pressure (P19.20) is greater than auxiliary
pressure start protection threshold (P15.01).
0.30MPa
○
P15.02
Stop delay of
auxiliary pressure
start protection
0
–300s
When the auxiliary pressure start protection is
enabled (P15.00=1), after the stopping delay
(P18.14) is reached, if the present auxiliary
pressure is still greater than the value set in
P15.01, the VFD continues to keep running at
no-load frequency in the time set in P15.02,
and then stops.
P18.12
P18.14
P15.02
Frequency
Time
30s
○
P15.03
Pressure limit setting
after time reached
0.00
–P18.04MPa
When the accumulated running time (P19.16)
reaches the value set in P15.04, the pressure
cannot exceed the value set in P15.03, if it
exceeds, bit1 of P15.05 is set to 1.
0.50MPa
○
P15.04
Upper limit of
accumulated running
time
0
–65535h
The function is disabled when P15.04 is set to
0.
0
○
P15.05
Device status flag
Bit0: Auxiliary pressure high flag
0: None
1: Auxiliary pressure is high, and the VFD is not
allowed to start
Bit1: Max. set pressure limited flag
0: None
1: Function is limited, please contact the factory
service.
0
●
P15.06
Auxiliary pressure
detection delay
0
–65535s
Note:
When P15.06 is set to 0, it indicates that
auxiliary pressure too low fault is not detected.
0
○