Goodrive300-01A series VFD for air compressor
Function code description
-80-
Function
code
Name
Description
Default Modify
power-frequency fan (SPOF)
0: Coast to stop
1: Run at alternative frequency of P21.10
P21.10 Alternative frequency 0.0
–100.0% (max. output frequency)
50.0%
○
P21.11
Running time of
alternative frequency
0.0
–6000.0s
Note:
When user-defined fault occurs to the
VFD, if the fault persists after the VFD
continues running at alternative frequency of
P21.10 in the time set by P21.11, the VFD will
coast to stop; if the fault no longer occurs
during P21.11, the VFD restores to normal
mode.
60.0s
○
P21.13
Display current of A
phase of the fan
0.0
–40.0A
0.0A
●
P21.14
Display current of B
phase of the fan
0.0
–40.0A
0.0A
●
P21.15
Display current of C
phase of the fan
0.0
–40.0A
0.0A
●
P21.20
Fan state
0X0000
–0XFFFF
Bit0: when it is 1, it means power-frequency
fan is started
0x0000
●