Goodrive300-01A series VFD for air compressor
Function code description
-38-
Function
code
Name
Description
Default Modify
P02.22
Quadrature-axis
inductance of SM 1
0.01
–655.35mH
Depend
on model
○
P02.23
Counter-emf constant
of SM 1
0
–10000
350
○
P02.26
Overload protection
selection of motor 1
0: No protection
1:
Normal
motor
(with
low
speed
compensation)
2: Variable-frequency motor (without low
speed compensation)
2
◎
P02.27
Overload protection
coefficient of motor 1
Motor overload multiple M = Iout/(In*K)
In is rated motor current, Iout is VFD output
current, K is motor overload protection
coefficient.
The smaller the K is, the larger the value of M
is; the smaller the value of M is, the easier the
protection is.
When M=116%, protection is performed after
motor overload lasts for 1 hour; when
M=150%, protection is performed after motor
overload lasts for 12 minutes; when M=180%,
protection is performed after motor overload
lasts for 5 minutes; when M=200%, protection
is performed after motor overload lasts for 60
seconds; and when M
≥400%, protection is
performed immediately.
1
5
12
60
116%
200%
Time (min)
Motor overload
multiple
150%
180%
Setting range: 20.0%
–120.0%
100.0%
○
P02.28
Power calibration
coefficient of motor 1
0.00
–3.00
1.00
○
P02.29
Parameter display
selection of motor 1
0: Displayed according to the motor type
1: All displayed
0
○