Goodrive300-01A series VFD for air compressor
Function code description
-54-
Function
code
Name
Description
Default Modify
potentiometer integral function
0: The integral function is valid
1: The integral function is invalid
P08.43
Integral time of digital
potentiometer
0.01
–10.00s
0.10s
○
P08.44
UP/DOWN terminal
control setup
0x00
–0x221
LED ones: Frequency enabling selection
0: UP/DOWN terminal setup is valid
1: UP/DOWN terminal setup is invalid
LED tens: Frequency control selection
0: Valid only when P00.06 =0
1: All frequency modes are valid
2: Invalid for multi-step speed when multi-step
speed takes priority
LED hundreds: Action selection during stop
0: Setting is valid.
1: Valid during running, cleared after stop
2: Valid during running, cleared after a stop
command is received
0x000
○
P08.45
UP terminal frequency
incremental change
rate
0.01
–50.00Hz/s
0.50Hz/s
○
P08.46
DOWN terminal
frequency decremental
change rate
0.01
–50.00Hz/s
0.50Hz/s
○
P08.47
Action selection for
frequency setup during
power down
0x000
–0x111
LED ones: Action selection at power-off
during frequency adjusting through digitals.
0: Save the setting at power-off.
1: Clear the setting at power-off.
LED tens: Action selection at power-off during
frequency
adjusting
through
Modbus
communication
0: Save the setting at power-off.
1: Clear the setting at power-off.
LED hundreds: Action selection at power-off
during frequency adjusting through other
communication
0: Save the setting at power-off.
0x000
○