Goodrive300-01A series VFD for air compressor
Function code description
-61-
Function
code
Name
Description
Default Modify
P14.02
Data bit check setup
0: No parity check (N, 8, 1) for RTU
1: Even parity (E, 8, 1) for RTU
2: Odd parity (O, 8, 1) for RTU
3: No parity check (N, 8, 2) for RTU
4: Even parity (E, 8, 2) for RTU
5: Odd parity (O, 8, 2) for RTU
1
○
P14.03
Communication
response delay
0
–200ms
5ms
○
P14.04
Communication
timeout fault time
0.0 (invalid), 0.1
–60.0s
0.0s
○
P14.05
Transmission error
processing
0
–4
0: Alarm and coast to stop
1: Do not alarm and continue running
2: Do not alarm and stop as per stop mode
(under communication control mode only)
3: Do not alarm and stop as per stop mode
(under all control modes)
4: Alarm and coast to stop, and automatic
fault reset after communication is restored
0
○
P14.06
Communication
processing action
selection
0x000
–0x111
LED ones: write operation action
0: There is response for write operation
1: There is no response for write operation
LED tens: Communication encryption
processing
0: Communication encryption setting is invalid
1: Communication encryption setting is valid
LED hundreds: Communication CRC check
failure handling
0: Return error type 06
1: Do not return any data (This function is
used with the Plot controller)
0x00
○
P15 group Non-standard functions
Function
code
Name
Description
Default Modify
P15.00
Auxiliary pressure
start protection
enable
0: Disable
1: Enable
0
◎