Goodrive300-01A series VFD for air compressor
Function code description
-72-
Function
code
Name
Description
Default Modify
by setting BIT10 of P19.14 to 1, and
emergency-stop will be applied.
P18.37
Pressure sensor
channel
0: Discharge pressure P1, auxiliary pressure
P2
1: Discharge pressure P2, auxiliary pressure
P1
2: Pressure display in normal VFD mode
(P18.00=0) (main pressure P1, auxiliary
temperature P2)
0
◎
P18.38
Upper limit of pressure
sensor P2
0.00
–20.00 Mpa
It is related to the actual range of pressure
sensor, the corresponding voltage of P18.04
is P05.44.
Note:
When restoring to default values, the
value will stay in current value.
1.60Mpa
◎
P18.39
Auxiliary pressure
protection enable
0: Invalid
1: Valid
0
◎
P18.40
Auxiliary pressure
pre-alarm
0.00
–20.00
When P18.39 is enabled and the auxiliary
pressure is larger than P18.40, the system
indicates auxiliary pressure pre-alarm by
setting BIT7 of P19.14 to 1.
0.90Mpa
○
P18.41
Auxiliary pressure
alarm
0.00
–20.00
When P18.39 is enabled and the auxiliary
pressure is larger than P18.41, the system
indicates pressure alarm by setting BIT9 of
P19.14 to 1, and emergency stop will be
applied.
1.00Mpa
○
P18.42
Fan frequency
reference mode
0: Temperature PID
1: Analog P2- setting
2: RS485 communication
0
◎
P18.43
Fan control mode
0: Air compressor mode, the power-frequency
fan starts/stops as per the temperature;
1:
Terminal,
the
power-frequency
fan
starts/stops via terminals;
2: 485 communication (address 0X201B, write
1 to start, write 3 to stop)
0
◎