Goodrive300-01A series VFD for air compressor
External optional accessories
-128-
Master parameter
Initial value
Function
Running frequency
upper limit
50.00Hz
It indicates the upper limit of the output
frequency of the VFD.
Running frequency
lower limit
00.00Hz
It indicates the lower limit of the output
frequency of the VFD.
Loaded running
frequency lower limit
40.00Hz
It indicates the minimum working frequency that
is allowed to output when the pressure exceeds
the set value but does not reach the unloading
pressure during regulation.
Empty-load running
frequency
38.00Hz
It indicates the working frequency when the air
compressor is empty loaded.
ACC time
Model depended
It indicates the time taken by the VFD to
accelerate from 0Hz to the maximum frequency.
DEC time
Model depended
It indicates the time taken by the VFD to
decelerate from the maximum frequency to 0Hz.
2. You can edit parameters only after entering a correct administrator password.
03.17 16:02:35
Home
Please enter current password:
Return
Confirm
000
0
Figure B-33 Administrator password input interface
03.17 16:02:35
Home
Set value
Return
Confirm
Max Output Freq
xxx.x Hz
Max. 600.00 MPa
Min. 000.00 MPa
x
Figure B-34 Maximum output frequency setting interface