Goodrive300-01A series VFD for air compressor
Wiring instruction
-16-
A1 A2
POWER
R
S
T
P1
(+)
(-)
U
V
W
MOTOR
Figure 3-14 220
–315kW main circuit terminal diagram
Table 3-1 Screw specification and torque of main circuit terminals of a single VFD
Power range (kW)
Terminal screw specification
Torque of torque driver (N
·
m)
7.5
–15
M5
2.5
18.5
–37
M6
3.5
45
–110
M8
10
132
–200
M12
35
220
–315
M12
35
Table 3-2 Main circuit terminal description of a single VFD
Terminal
sign
Terminal name
Terminal function
11
–15kW
7.5kW and
18.5
–110kW
132kW and above
R, S, T
Main circuit power input
3PH
AC
input
terminal,
connected to the grid
P1
None
DC reactor terminal 1 P1, (+) connect to DC reactor
terminal
(+)
None
Reserved
DC reactor terminal 2
(-)
None
Reserved
Reserved
PB
None
Reserved
None
U, V, W
VFD output
3PH
AC
output
terminal,
connected to the motor
Ground terminal for safety protection
Each
machine
must
be
grounded. The grounding is
implemented through the two
PE terminals on the machine,
and the grounding resistance is
less than
10Ω.