Goodrive300-01A series VFD for air compressor
Function code description
-59-
Function
code
Name
Description
Default Modify
P11.08
Pre-alarm selection for
VFD/motor
overload/underload
0x000
–0x131
LED ones:
0:
Motor
overload/underload
pre-alarm,
relative to the motor rated current,
1: VFD overload/underload pre-alarm, relative
to the VFD rated current
LED tens:
0: The VFD keeps running after reporting an
overload/underload alarm.
1: The VFD keeps running after reporting an
underload alarm, but it stops running after
reporting an overload alarm.
2: The VFD keeps running after reporting an
overload alarm, but it stops running after
reporting an underload alarm.
3: The VFD stops running after reporting an
overload/underload alarm.
LED hundreds:
0: Always detect
1: Detect only in constant speed running
0x000
○
P11.13
Fault output terminal
action during fault
0x00
–0x11
LED ones:
0: Act during undervoltage fault
1: Do not act during undervoltage fault
LED tens:
0: Act during automatic reset period
1: Do not act during automatic reset period
0x00
○
P11.14
Speed deviation
detection value
0.0
–50.0%
10.0%
○
P11.15
Speed deviation
detection time
0.0
–10.0s (Speed deviation protection is
disabled when P11.15 is set to 0.0)
0.5s
○
P11.16
Automatic frequency
reduction during
voltage drop
0: Invalid
1: Valid
1
○