Goodrive300-01A series VFD for air compressor
Fault information and troubleshooting
-97-
P19.14
State type
Possible cause
Solution
Temperature detection sensor
is abnormal.
Temperature detection input
circuit is abnormal.
BIT7=1
Auxiliary pressure
pre-alarm
The actual voltage
detected by P2 is larger
than the pre-alarm
pressure set by P18.17
Pressure detection sensor is
abnormal.
The pressure is set to a too
large value.
Adjust pressure PID regulator.
BIT8=1
Auxiliary temperature
pre-alarm
The actual temperature
detected by PT2 is
larger than the
pre-alarm temperature
set by P18.19
Temperature detection sensor
is abnormal.
Temperature detection input
circuit is abnormal, if not
calibrated.
The starting temperature of
the fan is set to a too high
value.
The temperature of the fan is
set to a too high value.
Fan power is too small to
dissipate heat effectively.
BIT9=1
Auxiliary pressure
alarm
The actual voltage
detected by P2 is larger
than the alarm pressure
set by P18.18.
Pressure detection sensor is
abnormal.
The voltage is set to a too high
value.
Adjust pressure PID regulator.
BIT10=1
Auxiliary temperature
alarm
The actual temperature
detected by PT2 is
higher than the alarm
temperature set by
P18.20.
Temperature detection sensor
is abnormal.
Temperature detection input
circuit is abnormal, if not
calibrated.
The starting temperature of
the fan is set to a too high
value.
The temperature of the fan is
set to a too high value.
The fan power is too small to
dissipate heat effectively.