Goodrive300-01A series VFD for air compressor
Commissioning instruction
-32-
Function
code
Name
Parameter
setting
Remarks
P05.01
S1 terminal
function selection
1
1: Forward running
P05.02
S2 terminal
function selection
49
49: Solenoid valve control signal
P05.03
S3 terminal
function selection
50
50: Cooling fan control signal of main motor
P06.02
RO1 output
selection
5
5: VFD fault
P14.00
Local
communication
address
1
Broadcast address: 1, distinguishing the main motor
VFD.
P18.43
Fan control mode
1
1: Terminal, the power-frequency fan starts/stops
via terminals;
4.4 Commissioning guidance for single-VFD integrated machine
485+
485-
GND
+24V
CGND/PE
485-
GND
+24V
485+
U2 V2 W2
Co o ling
fa n
S2
COM
U1 V1 W1
Ma in
mo to r
CN11
48 5-
48 5+
HMI
W ire le s s d a ta
co lle c tion te rm in a l
Discharge
pressure
Auxiliary
pressure
P2+
P2-
P1-
Auxiliary
temperature
PT100
Oil gas
temperature
PT100
PTA2
PTB2
P1+
PTA1
PTB1
COM
Motor overtemperature
Emergency stop
S1
S2
S4
S5
COM
R
S
T
R
S
T PE
M
M
GD 3 00 -0 1 A-C T
sin g le-V F D in te g ra te d
machine 7.5–15KW
R
S
0V
110V
220V
RO1
220V/TAH
110V/TAL
0V/TC
Solenoid
valve coil
Figure 4-17 Wiring diagram for single-VFD integrated machine system